概述
| 温度 | -40 ℃~+85 ℃ |
| 相对湿度 | 5%~95% (+25 ℃) |
| 海拔高度 | -500 m~+3000 m |
技术指标
| 型号 | ZGGF25-385(3+1)AYc | ZGGF25-385(4+0)AYc | ZGGF25-385(3+0)AYc | ZGGF25-385(1+1)AYc | ZGGF25-385(2+0)AYc |
| SPD按照IEC 61643-11 | Class Ⅰ+ Class Ⅱ | ||||
| SPD按照EN 61643-11 | Type 1+Type 2 | ||||
| 端口数量(接入模式) | 一端口(并联) | ||||
| 标称工作电压Uo | 230 V 50/60 Hz | ||||
| 持续运行电压 Uc | 385 V(L-N), 255 V(N-PE) 50/60 Hz | 385 V(L-PE, N-PE) 50/60 Hz | 385 V(L-PE) 50/60 Hz | 385 V(L-N), 255 V(N-PE) 50/60 Hz | 385 V(L-PE, N-PE) 50/60 Hz |
| 低压系统类型 | TN | TN-S | TN-C | TN-S | TN |
| 保护模式 | L-N, N-PE | L-PE, N-PE | L-PE | L-N, N-PE | L-PE, N-PE |
| 标称放电电流 In (8/20μs) | 25 kA (L-N), 100 kA (N-PE) | 25 kA(L-PE, N-PE) | 25 kA(L-PE) | 25 kA (L-N), 50 kA (N-PE) | 25 kA(L-PE, N-PE) |
| 冲击放电电流Iimp (10/350μs) | 25 kA (L-N), 100 kA (N-PE) | 25 kA(L-PE, N-PE) | 25 kA(L-PE) | 25 kA (L-N), 50 kA (N-PE) | 25 kA(L-PE, N-PE) |
| 电荷量Q | 12.5 As (L-N), 50 As (N-PE) | 12.5 As(L-PE, N-PE) | 12.5 As(L-PE) | 12.5 As (L-N), 25 As (N-PE) | 12.5 As(L-PE, N-PE) |
| 比能量 W/R | 156 kJ/Ω (L-N), 2500 kJ/Ω (N-PE) | 156 kJ/Ω(L-PE, N-PE) | 156 kJ/Ω(L-PE) | 156 kJ/Ω (L-N), 625 kJ/Ω (N-PE) | 156 kJ/Ω(L-PE, N-PE) |
| 测量限制电压 UL ( at Iimp) | ≤0.8 kV (after 10 μs, L-N) ≤1.0 kV (after 10 μs, N-PE) | ≤0.8 kV (after 10 μs, L-PE, N-PE) | ≤0.8 kV (after 10 μs, L-PE) | ≤0.8 kV (after 10 μs, L-N) ≤0.5 kV (after 10 μs, N-PE) | ≤0.8 kV (after 10 μs, L-PE, N-PE) |
| 电压保护水平 UP | 2.5 kV (L-N), 2 kV (N-PE) | 2.5 kV(L-PE, N-PE) | 2.5 kV(L-PE) | 2.5 kV (L-N), 1.5 kV (N-PE) | 2.5 kV(L-PE, N-PE) |
| 供电电源的预期短路电流Ip | 2 kA | ||||
| 续流遮断能力 Ifi | 2 kA (at 385 V a.c.) (L-N) 0.1 kA (at 255 V a.c.) (N-PE) | 2 kA (at 385 V a.c.)(L-PE, N-PE) | 2 kA (at 385 V a.c.)(L-PE) | 2 kA (at 385 V a.c.) (L-N) 0.1 kA (at 255 V a.c.) (N-PE) | 2 kA (at 385 V a.c.)(L-PE, N-PE) |
| 响应时间 tA | ≤100 ns (L-N, N-PE) | ≤100 ns(L-PE, N-PE) | ≤100 ns(L-PE) | ≤100 ns (L-N, N-PE) | ≤100 ns(L-PE, N-PE) |
| 泄漏电流 | ≤3 mA (L-N) | ≤3 mA(L-PE, N-PE) | ≤3 mA(L-PE) | ≤3 mA (L-N) | ≤3 mA(L-PE, N-PE) |
| 剩余电流 IPE | ≤3 mA | ||||
| 电源侧的过电流保护 | 250 A gL/gG | ||||
| 应用场合 | 室内 | ||||
| 外壳防护等级 | IP 20(安装后) | ||||
| 安装方式 | 35 mm 标准导轨 | ||||
| 状态指示操作 | Green: OK; Off: Replace | ||||
| 电源接线端子可夹紧导线面积 | 6 mm2~25 mm2线缆 | ||||
| 扭矩:接线端子/遥信接口 | 2.5 Nm/0.25 Nm | ||||
| 遥信接线参数 | Max. : 250V/0.1A ( a.c.) , min. : 12V/1mA ( a.c.) Max. : 30V/0.1A ( d.c.) , min. : 12V/1mA ( d.c.) | ||||
| 遥信接口可夹紧导线面积 | 0.15 mm2~1.3 mm2 | ||||
| 外壳材质 | PC | ||||
| 外壳阻燃等级 | UL94 V0 | ||||
| 储存期 | 2年 | ||||
| 质保期 | 2年 | ||||