MKVV国标电缆MKVV22矿用控制电缆10*2.5
供应MVV-3*2.5矿用塑料电力电缆MVV
型号 | 规格 | 导电线芯mm | zui大直流电阻20℃ | 载流量A | |||
铜芯Ω/km | 镀锡铜芯Ω/km |
|
|
| |||
|
|
|
|
|
|
| |
3×2.5+1×1.5 | 49/0.2530/0.25 | 7.98 | 8.21 | 26 |
| ||
3×4+1×2.5 | 56/0.3049/0.25 | 4.95 | 5.09 | 34 |
| ||
3×6+1×4 | 84/0.3056/0.30 | 3.30 | 3.39 | 43 |
| ||
3×10+1×6 | 84/0.4084/0.30 | 1.91 | 1.95 | 63 |
| ||
3×16+1×6 | 126/0.4084/0.30 | 1.21 | 1.24 | 84 |
| ||
3×25+1×10 | 196/0.4084/0.40 | 0.780 | 0.795 | 115 |
| ||
3×35+1×10 | 276/0.4084/0.40 | 0.554 | 0.565 | 142 |
| ||
3×50+1×16 | 396/0.40126/0.40 | 0.386 | 0.393 | 176 |
| ||
3×70+1×25 | 360/0.50196/0.40 | 0.272 | 0.277 | 224 |
| ||
3×95+1×35 | 475/0.50276/0.40 | 0.206 | 0.210 | 273 |
| ||
3×120+1×35 | 600/0.50276/0.40 | 0.161 | 0.164 | 316 |
| ||
3×150+1×50 | 756/0.50396/0.40 | 0.129 | 0.132 | 454
|
|
(1)切断起火电缆电源。电缆着火燃烧,无论何原因引起,都应立即切断电源,然后,根据电缆所经过的路径和特征,认真检查,找出电缆的故障点,同时应迅速组织人员进行扑救。
(2)电缆沟内起火非故障电缆电源的切断。当电缆沟中的电缆起火燃烧时,如果与其同沟并排敷设的电缆有明显的着火可能性,则应将这些电缆的电源切断。电缆若是分层排列,则首先将起火电缆上面的受热电缆电源切断,然后将与起火电缆并排的电缆电源切断,zui后将起火电缆下面的电缆电源切断。
(3)关闭电缆沟隔火门或堵死电缆沟两端。当电缆沟内的电缆起火时,为了避免空气流通,以利迅速灭火,应将电缆沟的隔火门关闭或将两端堵死,采用窒息的方法灭火。
(4)做好扑灭电缆火灾时的人身防护。由于电缆起火燃烧会产生大量的浓烟和毒气,扑灭电缆火灾时,扑救人员应戴防毒面具。为防止扑救过程中的人身触电,扑救人员还应戴橡皮手套和穿上绝缘靴,若发现高压电缆一相接地,扑救人员应遵守:室内不得进入距故障点4m以内,室外不得进入距故障点8m以内,以免跨步电压及接触电压伤人。救护受伤人员不在此限,但应采取防护措施。
(5)扑灭电缆火灾采用的灭火器材。扑灭电缆火灾应采用灭火机灭火,如干粉灭火机、“1211”灭火机、二氧化碳灭火机等;也可使用干砂或黄土覆盖;如果用水灭火,使用喷雾水枪;若火势猛烈,又不可能采用其他方式扑救,待电源切断后,可向电缆沟内灌水,用水将故障封住灭火。
(6)扑救电缆火灾时,禁止用手直接触摸电缆钢铠和移动电缆