详细介绍
10KVA/150KV油侵式试验变压器技术规格:
规格型号 | 容量(kVA) | 高压电压(kV) | 高压电流(mA) | 低压输入 | 变比(高/仪) | 温升℃(30分钟) | |
电压(V) | 电流(A) | ||||||
YD-1.5/50 | 1.5 | 50 | 30 | 200 | 7.5 | 500 | 10 |
YD-3/50 | 3 | 50 | 60 | 200 | 15 | 500 | 10 |
YD-5/50 | 5 | 50 | 100 | 200 | 25 | 500 | 10 |
YD-10/50 | 10 | 50 | 200 | 200 | 50 | 500 | 10 |
YD-20/50 | 20 | 50 | 400 | 400 | 53 | 500 | 10 |
YD-30/50 | 30 | 50 | 600 | 400 | 79 | 500 | 10 |
YD-50/50 | 50 | 50 | 1000 | 400 | 12 | 500 | 10 |
YD-5/100 | 5 | 100 | 50 | 200 | 25 | 1000 | 10 |
YD-10/100 | 10 | 100 | 100 | 200 | 50 | 1000 | 10 |
YD-20/100 | 20 | 100 | 200 | 400 | 53 | 1000 | 10 |
YD-30/100 | 30 | 100 | 300 | 400 | 79 | 1000 | 10 |
YD-50/100 | 50 | 100 | 500 | 400 | 132 | 1000 | 10 |
YD-20/150 | 20 | 150 | 133 | 400 | 53 | 1500 | 10 |
YD-30/150 | 30 | 150 | 200 | 400 | 80 | 1500 | 10 |
YD-50/150 | 50 | 150 | 333 | 400 | 132 | 1500 | 10 |
YD-100/150 | 100 | 150 | 667 | 400 | 263 | 1500 | 10 |
YD-50/200 | 50 | 200 | 250 | 400 | 132 | 2000 | 10 |
YD-100/200 | 100 | 200 | 500 | 400 | 263 | 2000 | 10 |
YD-150/200 | 150 | 200 | 750 | 400 | 395 | 2000 | 10 |
YD-200/200 | 200 | 200 | 1000 | 400 | 526 | 2000 | 10 |
YD-300/200 | 300 | 200 | 1500 | 400 | 790 | 2000 |
10KVA/150KV油侵式试验变压器注意事项:
1、做高压试验时,必须由2人或2个以上人员参加,并明确做好分工,明确相互间的方法。并有专人监护现场安全及观察试品的试验状态;
2、变压器和控制箱应有可靠的接地;
3、试验过程中,升压速度不能太快,也决不允许突然全电压通电或断电;
4、在升压或耐压试验过程中,如发现下列不正常情况时,应立即降压,并切断电源,停止试验,查明原因后再做试验。① 电压表指针摆动很大;② 发现绝缘烧焦的异味、冒烟现象;③ 被测试品内有不正常的声音。
5、试验中,如果试品短路或故障击穿,控制箱中的过流继电器工作,此时,将调压器回至零位,并切断电源后,方可将试品取出。
6、进行电容试验或进行直流高压泄漏试验时,试验完毕后,将调压器降至零位后,并切断电源,然后,应用放电棒将试品或电容器的高压端对地进行放电,以免存留在电容中的电势发生触电危险
技术及参数:
额定容量:20KVA
相数:单相
频率:50HZ
额定电压:输入电压:0.38KV 输出电压:0~ 0.43KV
额定电流:输入电流:52.6A 输出电流:0~46.5A
调压方式:手动调压
运行时间:同变压器
起始电压:≤1%
波形畸变率:≤3%
阻抗电压:全程阻抗变化范围≤10%
体积:长500mm宽600mm高850mm