通信电缆 网络设备 无线通信 云计算|大数据 显示设备 存储设备 网络辅助设备 信号传输处理 多媒体设备 广播系统 智慧城市管理系统 其它智慧基建产品
扬州市金鑫电缆有限公司
耐高温(阻燃)电力电缆HeatResisting(Flameretardant)PowerCable一、适用范围本产品适用于额定电压0.6/1kV及以下的高温范围和恶劣环境内,作电气设备电能传输线
耐高温(阻燃)电力电缆Heat Resisting(Flame retardant) Power Cable
一、适用范围
本产品适用于额定电压0.6/1kV及以下的高温范围和恶劣环境内,作电气设备电能传输线。
Scope ofapplication
It is used as power transmission cable for electric equipmentsof rated voltage 0.6/1kV or lower in bad environment or thatwith high temperature.
二、执行标准
企业标准
TICW/03-2009
Executive standard
Enterprise standard
TICW/03-2009
三、使用特性
1、额定电压Uo/U: 0.6/1kV。
2、电缆允许**工作温度: 氟塑料绝缘及护套为200C氟塑料绝缘耐热105聚氯乙烯护套为105C:氟塑料绝缘硅橡胶护套
为180C。
3、短路时(最长持续间不超过5S)电缆导体的**温度不超过250C。
4、电缆敷设温度应不低于-15C5、电缆的弯曲半径如下:单芯电缆: 其弯曲半径不小于 电缆外径的20D。
三芯电缆:其弯曲半径不小于电缆外径的15D6、氟塑料绝缘及护套型电力电缆具有优异的耐化学腐蚀性、耐高温及阻燃性。
Performance in Usage
1: Rated voltage Uo/U: 0.6/1kV
2: Max.working temperature allowed by cable is 200C forcable with fluoroplastic insulation and sheath,105C for cablewith fluoroplastic insulation, 105C heat resistanc and PVCsheath, and 180C for cable with fluo- roplastic insulation andsilicon rubber sheath.
3: Max temperature of cable conductor is no more than 250Cduring short circuit (The longest lasting time is no more than 5s).
4: Temperature for installation is no less than -15C.5: Bending radius of cable as followsIt is no less than 20 times that of cable outer diam- eter forcable with single core It is no less than 15 times that of cableouter diameter for cable with 3 cores6: Power cable with fluoroplastic insulation and sheath hasgood features of chemical corrosion resis- tance hightemperature resistance and flame retardance.
四、电缆的型号名称 Type and Description
1、电缆的型号名称如表1 Type and Description in Table 1
Table 1
注:型号中“22"表示钢带铠装,如需钢丝铠装结构应将型号中的“22"改为“32"即可。
Note: 22 means steel tape armor “22" should be changed into “32" for cable with steel wire armor (if needed).
五、电缆规格
电缆规格表示为芯数X导体标称截面mm’,其芯数及导体标称截面如表2
Specification of Cable
“core number * nominal cross section" stands forcable specification. Please see the following table 2 forcore number and nominalcross section
Table 2
六、技术参数
1、20C导体直流电阻应符合GB/T3956标准规定
2、电缆应经受3500V交流耐压试验5min绝缘不击穿
Technical Parameter
1: DC resistance of conductor at 20C shall meet therequirement of GB/T3956 standard.
2: Cable shall bear AC voltage test of 3500V for 5minwithout puncture of insulation.
您感兴趣的产品PRODUCTS YOU ARE INTERESTED IN
智慧城市网 设计制作,未经允许翻录必究 .
请输入账号
请输入密码
请输验证码
请输入你感兴趣的产品
请简单描述您的需求
请选择省份